Ampliar
S8610U Honeywell
- Sacar de mis favoritos
- Agregar este producto a mis favoritos
- Enviar a un amigo
- Imprimir
Quick Overview
S8610U Honeywell
MODULO DE IGNICION
Ampliar
S8610U Honeywell
MODULO DE IGNICION
S8610U Honeywell
MODULO DE IGNICION
ESPECIFICACIONES DE PRODUCTO:
Dimensiones (in.) 3 15/16 in. high x 5 7/16 in. wide x 2 5/8 in. deep
Dimensiones (mm) 100 mm high x 138 mm wide x 67 mm deep
Incluye Damper connection with automatic vent damper plug
Electrical Ratings 24 Vac
Frequency 60 Hz
Approvals, Canadian Standards Association Design Certified
Tradeline Value Tradeline
Flame Failure Response Time (sec) 2 seconds maximum
PrePurge Configurable to 30 seconds or no prepurge
Ambient Temperature Range (F) -40 F to +165 F
Ambient Temperature Range (C) -40 C to +74 C
Ignition System Type Intermittent Pilot
Ignition Sequence Continuous Retry
Typical Gas Control VR8204, VR8304
Type of Gas Natural or LP
Flame Sense Single Rod or Two Rods
Ignition Source Internal high voltage spark generator
Ignition Trials To Lockout continuous retry
Lockout Timing continuous retry
Ignition Trial Time (sec) 15 or 90 sec
Maximum Valve Load @ 24 Vac (Amps) 1A Pilot, 2A Main @ 165 F; 1A Pilot, 1A Main @ 175 F
Typical Ignition Hardware Q345, Q3451, Q3452
Between Trial Time (sec) 5 minute delay after failed trial for ignition.